800 VDC Power Gives AI Data Centres Flexible Options

Vertiv has added 800 VDC power systems for AI compute pods and data halls, which expands its rack-level range. The range began in May 2026 with the PowerDirect 5000 Power Rack, so operators now have three places to start. VDC means volts of direct current, a power type some AI sites are testing to support denser computing. Vertiv says operators can add it step by step, without moving a whole data centre to one design.

Vertiv expects 800 VDC power and traditional AC power to share data centres for some time. This because operators have different needs. Scott Armul, Vertiv’s Chief Product and Technology Officer, says the 800 VDC approach is a set of system designs, not one product. Every layer, from the medium-voltage grid to the compute tray, must work together, with safety built for DC.

800 VDC power

800 VDC Power at The Rack, Pod and Data Hall

At rack level, the PowerDirect 5000 sits beside the IT rack and supplies 800 VDC power from a facility 480 VAC feed. Configurable up to 800 kW, it holds 30 power supply units and a battery unit with at least 50 seconds of backup. Because it moves conversion and storage out of the IT rack, operators can free 8 to 16 rack units for more computing. Operators can keep their existing AC equipment upstream, which suits older sites and mixed AC and DC setups.

At pod level, the PowerDirect 9000 converts 480 VAC to 800 VDC power for a whole row. It uses one 1.5 MW system. It scales in 60 kW steps, and a battery cabinet adds 200 kW of backup, with up to six cabinets working together. At data hall level, the 5 MW PowerNexus MV SST turns medium-voltage AC straight into 800 VDC in one step. Vertiv says this skips two to three conversion steps in conventional designs and reaches up to 98% efficiency.

Safety Built for DC and What Comes Next

Vertiv says 800 VDC power needs safety methods built for DC, not copied from older AC systems. Its 800 VDC designs include touch-proof busbars, high-voltage isolation, midpoint grounding, ground-fault detection and arc-flash prevention. Kyle Keeper of Vertiv’s Power Management unit says each operator can pick the approach that fits its sites. Vertiv says pilot programmes, technical validation and joint development work with customers are already under way.